Troubleshoot with the Indicators

The ArmorBlock I/O module has 2 types of indicators:

Mod/Net status indicator

individual I/O status indicators

Mod/Net Status Indicator

MOD/NET

STATUS

NODE

ADDRESS

DA

TA

RA

TE

ARMORBLOCK I/O

1792-OB4E

Output I/O Status Indicators

Mod/Net Status Indicator

Indication

Status

OFF

No power, or no network access, or incorrect baud rate

1

Flashing Green/OFF

On-line but not connected

Solid Green

On-line, link okay, connected

Flashing Red

Recoverable fault

Solid Red

Critical failure, or duplicate node address present

Green to Red to Off

At powerup only – The module is autobauding

1

This only occurs when Autobaud is disabled, and the module is set to an incorrect baud rate.

Output I/O Status Indicator

Indication

Status

OFF

Output is off

Yellow

Output is on

Red (see note)

Output is faulted

Note: A faulted output may cause adjacent outputs to fault.