Connecting the Output Wiring

Connect individual output wiring to micro connectors which screw into
mating connectors on the side of the block. Make connections as shown
below.

1

2

3

4

I/O Output Micro Connector

Pin 1 = Not used

Pin 2 = Not used

Pin 3 = Negative

Pin 4 = Output

(View into socket)

Connect the output power wiring to the 3-pin mini connector on the end
of the block.

Important:

The outputs use electronic overcurrent fault protection. Make certain
your output power supply can handle overcurrent events.

1

2

3

Output Power Mini Connector

Pin 1 = Not used

Pin 2 = Positive

Pin 3 = Negative

(View into pins)

Connecting the DeviceNet Wiring

Connect DeviceNet wiring to the 5-pin mini connector on the end of
the block. Connections are shown below.

1

2

3

DeviceNet Mini Connector

Pin 1 = Drain (Bare)

Pin 2 = V+ (Red)

Pin 3 = V– (Black)

(View into pins)

4

5

Pin 4 = CAN–HI (White)

Pin 5 CAN–LO (Blue)

Note: Colors are
DeviceNet standard

Advertising