18 POINT I/O 120V AC Input Module

Publication 1734-IN010D-EN-E - March 2013

Indicator Status for Modules

Status

Description

Recommended Action

Network status Off

Device is not online:

- Device has not completed
dup_MAC-id test.

- Device not powered – check
module status indicator.

Apply power to device, wait for
MAC_id to complete, and
correct as needed.

Flashing green

Device is online but has no
connections in the established
state.

None – device is in idle or
program mode.

Green

Device is online and has
connections in the established
state.

None.

Flashing red

One or more I/O connections are
in timed-out state.

Check for I/O module failure,
and correct as needed.

Red

Critical link failure – failed
communication device. Device
detected error that prevents it
from communicating on the
network.

Verify that adapter and terminal
bases are properly installed, and
reinstall as needed.

Flashing red/green Communication faulted device –

the device has detected a
network access error and is in
communication faulted state.
Device has received and
accepted an Identity
Communication Faulted Request
– long protocol message.

Verify that adapter is properly
installed, and reinstall as
needed.

I/O status

Off

Input is in the off state.

None.

Yellow

Input is in the on state.

None.