Environmental specifications, General specifications – Rockwell Automation 1734-IA2_IA4, Series C POINT I/O 120V AC Input Module Installation Instructions User Manual

Page 20

Advertising
background image

20 POINT I/O 120V AC Input Module

Publication 1734-IN010D-EN-E - March 2013

North American temp code

T4A

IEC temp code

T4

Enclosure type rating

None (open-style)

Delay time

(2)

Off to On and On to Off

20 ms hardware filter plus 1...64 ms digital filter programmable in
increments of 1 ms

Keyswitch position

8

(1)

Use this conductor category information for planning conductor routing as described in Industrial Automation Wiring
and Grounding Guidelines, publication

1770-IN041

.

(2)

Input off-to-on filter time is the time from a valid input signal to recognition by the module. Input on-to-off filter time is
the time from the input signal dropping below the valid level to recognition by the module. Due to the randomness of
the AC line-cycle measurement capture point and response time of the hardware filter, the maximum hardware delay is
20 ms plus the filter time.

Environmental Specifications

Attribute

Value

Temperature, operating

IEC 60068-2-1 (Test Ad, Operating Cold),
IEC 60068-2-2 (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal Shock):
-20...55 °C (-4...131 °F)

Temperature, nonoperating

IEC 60068-2-1 (Test Ab, Unpackaged Non-operating Cold),
IEC 60068-2-2 (Test Bb, Unpackaged Non-operating Dry Heat),
IEC 60068-2-14 (Test Na, Unpackaged Non-operating Thermal Shock):
-40...85 °C (-40...185 °F)

Relative humidity

IEC 60068-2-30 (Test Db, Unpackaged Damp Heat):
5...95% non-condensing

Vibration

IEC 60068-2-6 (Test Fc, Operating):
5 g @ 10...500 Hz

Shock, operating

IEC 60068-2-27 (Test Ea, Unpackaged Shock):
30 g

Shock, nonoperating

IEC 60068-2-27 (Test Ea, Unpackaged Shock):
50 g

Emissions

CISPR 11:

Group 1, Class A

ESD Immunity

IEC 61000-4-2:
6 kV contact discharges
8 kV air discharges

General Specifications