ControlLogix DeviceNet Scanner Module 39

Publication

1756-IN566D-EN-P - June 2008

Module Command Register Bit Definitions

The bits of the Module Command Register are defined as follows.

Bit

Name

Description

0

Run

1 = run mode

0 = idle mode

1

Fault

1 = fault network

2

DisableNetwork

1 = disable network

3

HaltScanner

1 = halt module
(the 1756-DNB scanner module ceases all
operation.)

4

Reset

1 = reset module

(put back to 0 to resume operation.)

5...31

Reserved

Unused

IMPORTANT

If the module is halted because the HaltScanner bit is set, power must be
physically recycled to restart the module.