Module command register bit definitions – Rockwell Automation 1756-DNB ControlLogix DeviceNet Scanner Module Installation Instructions User Manual
Page 39
Advertising
ControlLogix DeviceNet Scanner Module 39
Publication
1756-IN566D-EN-P - June 2008
Module Command Register Bit Definitions
The bits of the Module Command Register are defined as follows.
Bit
Name
Description
0
Run
1 = run mode
0 = idle mode
1
Fault
1 = fault network
2
DisableNetwork
1 = disable network
3
HaltScanner
1 = halt module
(the 1756-DNB scanner module ceases all
operation.)
4
Reset
1 = reset module
(put back to 0 to resume operation.)
5...31
Reserved
Unused
IMPORTANT
If the module is halted because the HaltScanner bit is set, power must be
physically recycled to restart the module.