Input structure – Rockwell Automation 1756-DNB ControlLogix DeviceNet Scanner Module Installation Instructions User Manual
Page 40
Advertising
40 ControlLogix DeviceNet Scanner Module
Publication
1756-IN566D-EN-P - June 2008
Input Structure
The controller receives input I/O by reading input data from an input
structure in the 1756-DNB scanner module. The scanner module receives
input data from DeviceNet modules and delivers a copy of these values to the
controller. The input structure consists of one 32-bit status register and a
variable size 32-bit array of up to 124 words for input data. The 32-bit status
register reflects the current state of several key module-level operational
parameters.
The input structure consists of these data elements.
Input Structure Element
Data Type
module status register
1 x 32-bit register
input_data
123 x 32-bit variable size data array