Chapter

6

Publication 1746-6.19 March 1998

Troubleshooting

This chapter:

Describes the module’s LED indicators

Suggests corrective action for typical operating problems

Use this table to interpret the module’s LED-indicated status.

HYDRAULIC

SYNCHR AXES

AXES 1

RUN/FLT

3

2

4

Module “Run” status:
Green:

Module OK

Off:

SLC not communicating

Flash Grn: Updating

FLASH

memory

Module ”Fault” status:
Red:

Fault or Power-up reset

Green:

Module power OK

Axis status (one LED per axis):
Red:

LDT error (loss of input, noise)

Green:

Axis OK

Flash Red: Axis motion error
Off:

Axis not initialized

Use this table to look up corrective action for typical problems.

Problem Condition:

Possible Cause:

Corrective Action – Check the Following:

Ladder program cannot:
– access parameters
– operate the module

You made errors configuring
the module or addressing
your ladder logic.

1) module is not configured properly
2) module’s I/O slot number and ladder address do not match

Red Axis LEDs are on

The transducer is not
responding to the module.

1) Status word to determine which transducer fault has occurred
2) Transducer power supply and wires to the transducer

During a move, the
Actual Position is erratic

Incorrect shielding or a
defective transducer is
causing electrical noise.

Monitor bits 13, 14, and 15 of the axis’

STATUS

word to determine if

the module is detecting a transducer error. To reduce electrical noise:
1) Make sure the transducer wiring is separated from all other wiring.
2) Add a termination resistor (220 ohm for Temposonics I) as close
to the transducer as possible.
3) Connect the shield at the module end, transducer end, or both.

During a move, the
drive halts for no apparent reason

When the module detects a
“transducer not responding”
error it stops automatically.

See “...Actual Position is erratic” above for more information.
If any of the following conditions are enabled, the axis will also halt:
– Following Error

– Position Overflow

– Integrator Windup

– Overdrive

– Parameter Error

Transducer counts field is not
indicating transducer location

See“’Red Axis LEDs are on” above.

Transducer counts field changes
but output drive does not work

See “...drive halts for no apparent reason” above.

The System is unresponsive
and hard to tune

This problem could have
several causes.

1) Is a hose rather than rigid pipe installed between the hydraulic
valve and the cylinder? The fluid expands the hose rather than
moving the cylinder.
2) Does the valve have overlap? Overlap in hydraulic valves causes
a significant dead band and slows the system response. Some
proportional valve amplifiers have dead band eliminator circuits
which make tuning easier.

The axis oscillates

This problem could have
several causes.

1) The

DEAD BAND ELIMINATOR

value may be too high.

2) Reduce

PROPORTIONAL, INTEGRAL,

or

DIFFERENTIAL

gains.

The axis does not finish moves or
moves differently than expected

The SLC processor is issuing
unintended commands.

Use the Hydraulics Configurator command queue to monitor
commands sent by the SLC processor to the module.
Confirm that only the expected commands are being sent.

Objectives

Using LED Indicators

Correcting
Typical Problems