Using Processor Files

C–2

Publication 1746-6.19 March 1998

Transferring Motion Commands and Axis Status

Motion commands and axis status can be integer or floating-point values.

Important: If your application requires position values > 32,767, you
must use floating-point values and your ladder logic instructions must:

compute floating-point numbers from integer

store values in floating-point (F) files

Each of four files contains the 8-word motion command for an axis.
The eight words define the axis’ motion profile. When directed by a
ladder logic command, ladder logic moves the files into the output
image table for transfer to the module. The example shows floating
point files with compute instructions.

Output Image Table

>>>

Axis 4 #F7:24

Axis 3 #F7:16

Axis 1 #F7:0

F files contain 8-word
motion-control commands

Mode
Accel
Decel
Speed
Position
Command
reserved (2)

>>>

>>>
>>>

1746-QS Module

Commands
for Motion
Profiles

>>>
>>>

>>>
>>>

Axis 2 #F7:8

Mode
Accel
Decel
Speed
Position
Command
reserved (2)

Ladder Logic
Compute FP
to Integer

Output
Image
Scan

When directed by a ladder logic command, ladder logic moves eight
words of axis status from the input image table to processor files.
The example shows floating-point with compute instructions and
floating-point files.

Input Image Table

>>>

Axis 4 #F7:24

Axis 3 #F7:16

Axis 1 #F7:0

N files contain
8 words of
axis status

Commanded Position
Target Position
Actual Position
LDT Counts
Status Bits
Drive Output
Actual Speed
Drive Null

>>>

>>>
>>>

1746-QS Module

>>>
>>>

>>>
>>>

Axis 2 #F7:8

Commanded Position
Target Position
Actual Position
LDT Counts
Status Bits
Drive Output
Actual Speed
Drive Null

Axis Status During
a Motion Profile

Input
Image
Scan

Ladder Logic
Computes FP
from Integer
and stores data
in F files.

Transferring Configuration Parameters

Configuration parameters are defined as integer (N) values.

Each of four N files contains the 16-word configuration parameters
for an axis. The 16 words define the axis’ static characteristics. At
power up or when directed by a ladder logic command, ladder logic
copies N files into the M0 file for transfer to the module.