Module status indicator – mod – Rockwell Automation 1732E-XXXX Ethernet/IP 24Vdc 16 Input Modules User Manual

Page 17

Advertising
background image

ArmorBlock 16-Point EtherNet/IP Module, Series A 17

Publication

1732E-IN002B-EN-E - February 2011

Module Status Indicator – MOD

Flashing
red

Connection time out

One or more connections
have timed out.

Reset connections to the
module.

Red

Duplicate IP

The module has detected
that its IP address is
already in use.

Resolve the IP address
conflict.

Flashing
red/green

Self-test in
progress

The module is performing
a powerup self-test.

None

State

Status

Description

Recommended Action

Off

Not powered

There is no power applied to
the device.

Apply power to the device.

Flashing
red/green

LED powerup
test

The module is performing a
powerup self-test.

None

Green

Module
operational

The module is operating
normally.

None

Flashing
red

Minor fault

The module has one of the
following recoverable
faults:

Firmware (NVS) update.

IP Address switches have

changed.

Check your configuration

and cycle power.

If a firmware update is in

progress, wait for it to
complete.

Verify that IP address

switches are set to the
desired value.

Solid red

Critical fault

The module has one of the
following unrecoverable
faults:

Self-test failure (checksum

failure or ramtest failure at
powerup).

Firmware fatal error.

Cycle power to the module.
If that does not fix the fault,
contact your Rockwell
Automation representative.
The module may need to be
replaced.

State

Status

Description

Recommended Action