Environmental specifications, General specifications – Rockwell Automation 1732E-XXXX Ethernet/IP 24Vdc 16 Input Modules User Manual

Page 21

Advertising
background image

ArmorBlock 16-Point EtherNet/IP Module, Series A 21

Publication

1732E-IN002B-EN-E - February 2011

Dimensions (HxWxD), approx.

179 x 65 x 43.25 mm
(7.05 x 2.56 x 1.70 in.)

Weight, approx.

0.34 kg (0.75 lb)

Enclosure type rating

Meets IP65/66/67/69K (when marked), and
NEMA 4X/6P with receptacle dust caps or
cable termination.

Isolation voltage

50V (continuous), Reinforced Insulation Type
Type tested @ 707V DC for 60 s, I/O to Ethernet,
Power to Ethernet

Wiring category

(1)

1 – on signal ports
1 – on power ports
2 – on communications ports

(1)

Use this Conductor Category information for planning conductor routing. Refer to publication

1770-4.1

,

Industrial Automation Wiring and Grounding Guidelines.

Environmental Specifications

Attribute

Value

Temperature, operating

IEC 60068-2-1 (Test Ad, Operating Cold),
IEC 60068-2-2 (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal Shock):
-20…60 °C (-4…140 °F)

Temperature, storage

IEC 60068-2-1 (Test Ab, Un-packaged Non-operating Cold),
IEC 60068-2-2 (Test Bb, Un-packaged Non-operating
Dry Heat),
IEC 60068-2-14 (Test Na, Un-packaged Non-operating
Thermal Shock):
-40…85 °C (-40…185 °F)

Temperature, ambient, max

60 °C (140 °F)

Relative humidity

IEC 60068-2-30 (Test Db, Un-packaged Damp Heat):
5…95% non-condensing