Mount the module – Rockwell Automation 1732E-XXXX Ethernet/IP 24Vdc 16 Input Modules User Manual

Page 7

Advertising
background image

ArmorBlock 16-Point EtherNet/IP Module, Series A 7

Publication

1732E-IN002B-EN-E - February 2011

of the module. Use a small blade screwdriver to rotate the switches. Line up
the small notch on the switch with the number setting you wish to use. Valid
settings range from 001...254.

Network Address Example

When the switches are set to a valid number, the I/O block’s IP address is
192.168.1.

xxx (where xxx represents the number set on the switches). The

I/O block’s subnet mask is 255.255.255.0 and the gateway address is set to
0.0.0.0. When the I/O block uses the network address set on the switches, the
I/O block does not have a host name assigned to it or use any Domain Name
Server.

If the switches are set to an invalid number–for example, 000 or a value
greater than 254 excluding 888–the I/O block checks to see if DHCP is
enabled. If DHCP is enabled, the I/O block asks for an address from a
DHCP server. The DHCP server also assigns other Transport Control
Protocol (TCP) parameters.

If DHCP is not enabled, the I/O block uses the IP address, along with other
TCP configurable parameters, stored in nonvolatile memory.

Mount the Module

Mount the module directly to a machine using two mounting holes, 5.3 mm
(0.208 in.) in diameter. Mounting holes accommodate #6 (M3) pan head
screws. The torque specification is 6.912 cm-kg (6 in-lbs).

This example shows
the network address
set at 163.

44233

Advertising