20 ArmorBlock 16-Point EtherNet/IP Module, Series A

Publication

1732E-IN002B-EN-E - February 2011

Current on-state output, max

0.5 A – 1732E-16CFGM12x
2 A – 1732E-OB16M12

Current per module, max

8.0 A (all outputs)

Leakage current, off-state output, max

50

μ

A

Surge current per output, max

3.2 A for 10 ms, repeatable every 2 s –
1732E-16CFGM12x
6 A for 10 ms, repeatable every 2 s –
1732E-OB16M12x

Pilot duty rating

DC-14 Pilot Duty

General Specifications

Attribute

Value

Voltage, auxiliary power, max

30V DC

Voltage, auxiliary power, min

12V DC

Current, auxiliary power input, max per
module (pins 2, 3)

1.1 A
0.3 A – 1732E-OB16M12

Current, auxiliary power, max per
module (pins 1, 4 plus pins 2, 3)

8 A (pins 2, 3 for sensor source and module plus
pins 1, 4 for output loads)

Current, sensor source, per input, max

50 mA

Current, sensor source, per module,
max (pins 2, 3)

800 mA

Communication rate

EtherNet/IP
10/100 Mbps
Full or half-duplex
100 meter per segment

LED indicators

Module status – red/green
Network status – red/green
Link status – green
Auxiliary power – green
I/O LED – yellow

ArmorBlock 2-Port EtherNet/IP Module – 1732E-16CFGM12x,
1732E-OB16M12