Interpret the status indicators – Rockwell Automation 1747-AENTR SLC to EtherNet/IP Adapter Installation Instructions User Manual

Page 12

Advertising
background image

12 SLC 500 EtherNet/IP Adapter

Publication 1747-IN521B-EN-E - January 2013

Interpret the Status Indicators

The four-character display indicates module status as shown in the table below.

Indicator

State

Description

Module

Off

No power applied to device

Green

Device operating normally

Flashing green

Device has not been configured

Flashing red

Recoverable fault.
IP Address switches do not match configuration in use.
The device has completed a reset to factory default request

because the switches were set to 888 at powerup, and a power
cycle is required.

The device is performing a firmware flash update.

Red

Unrecoverable fault, may require device replacement

4 Character Display

Displays IP address and module status description.
See table, Four-character Status Display, for a description of all the
possible module status.

Link 1 or Link 2

Off

No link established.

Solid green

Link established @ 100 Mbps.

Flashing green

Transmit or receive activity present on indicated port @ 100 Mbps.

Solid yellow

Link established @ 10 Mbps.

Flashing yellow

Transmit or receive activity present on indicated port @ 10 Mbps.

Four-character Status Display

MOD LED

Display

Description

Probable Cause

Recommended
Action

System startup

Red-green
flash
followed by
Solid Red

Dotted display on

Module is
performing Power On
Self Test (POST)

None

None

Green

“OK”
(The first scroll cycle
displays the software
revision in the format
"Rev
majorRev.minorRev.
subMinorRev
")

POST is successful

None

None

Red

4-digit error hex code
(For example, 0100 and
0101)

POST Failure
(0100 = IOFPGA
failure)
(0101=ESFPGA
failure)

The adapter has
either failed a
hardware test, or
gone into a state
from which it cannot
recover.

Document the
error codes.
Power cycle the
adapter. Contact
Technical
Support.

Advertising