North american hazardous location approval – Rockwell Automation 1747-AENTR SLC to EtherNet/IP Adapter Installation Instructions User Manual

Page 4

Advertising
background image

4 SLC 500 EtherNet/IP Adapter

Publication 1747-IN521B-EN-E - January 2013

North American Hazardous Location Approval

The 1747-AENTR module is North American Hazardous Location approved.

The following information applies when operating
this equipment in hazardous locations:

Informations sur l’utilisation de cet équipement en
environnements dangereux:

Products marked "CL I, DIV 2, GP A, B, C, D" are
suitable for use in Class I Division 2 Groups A, B, C,
D, Hazardous Locations and nonhazardous locations
only. Each product is supplied with markings on the
rating nameplate indicating the hazardous location
temperature code. When combining products
within a system, the most adverse temperature
code (lowest "T" number) may be used to help
determine the overall temperature code of the
system. Combinations of equipment in your system
are subject to investigation by the local Authority
Having Jurisdiction at the time of installation.

Les produits marqués "CL I, DIV 2, GP A, B, C, D" ne
conviennent qu'à une utilisation en environnements de
Classe I Division 2 Groupes A, B, C, D dangereux et non
dangereux. Chaque produit est livré avec des
marquages sur sa plaque d'identification qui indiquent
le code de température pour les environnements
dangereux. Lorsque plusieurs produits sont combinés
dans un système, le code de température le plus
défavorable (code de température le plus faible) peut
être utilisé pour déterminer le code de température
global du système. Les combinaisons d'équipements
dans le système sont sujettes à inspection par les
autorités locales qualifiées au moment de l'installation.

EXPLOSION HAZARD

Do not disconnect equipment unless
power has been removed or the area
is known to be nonhazardous.

Do not disconnect connections to this
equipment unless power has been
removed or the area is known to be
nonhazardous. Secure any external
connections that mate to this
equipment by using screws, sliding
latches, threaded connectors, or other
means provided with this product.

Substitution of any component may
impair suitability for Class I,
Division 2.

If this product contains batteries, they
must only be changed in an area
known to be nonhazardous.

RISQUE D’EXPLOSION

Couper le courant ou s'assurer que
l'environnement est classé non dangereux
avant de débrancher l'équipement.

Couper le courant ou s'assurer que
l'environnement est classé non dangereux
avant de débrancher les connecteurs.
Fixer tous les connecteurs externes reliés
à cet équipement à l'aide de vis, loquets
coulissants, connecteurs filetés ou autres
moyens fournis avec ce produit.

La substitution de tout composant peut
rendre cet équipement inadapté à une
utilisation en environnement de Classe I,
Division 2.

S'assurer que l'environnement est classé
non dangereux avant de changer les piles.

WARNING: When you insert or remove the module while backplane power is on, an
electrical arc can occur. This could cause an explosion in hazardous location
installations.
Be sure that power is removed or the area is nonhazardous before proceeding.
Repeated electrical arcing causes excessive wear to contacts on both the module and
its mating connector. Worn contacts may create electrical resistance that can affect
module operation.

WARNING: When used in a Class I, Division 2, hazardous location, this equipment
must be mounted in a suitable enclosure with proper wiring method that complies
with the governing electrical codes.