Environmental Specifications

Attribute

Value

Temperature, operating

IEC 60068-2-1 (Test Ad, Operating Cold),
IEC 60068-2-2 (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal Shock):
0…60 °C (32…140 °F)

Temperature, nonoperating

IEC 60068-2-1 (Test Ab, Unpackaged Non-operating Cold),
IEC 60068-2-2 (Test Bb, Unpackaged Non-operating Dry Heat),
IEC 60068-2-14 (Test Na, Unpackaged Non-operating Thermal Shock):
-40…85 °C (-40…185 °F)

Temperature, surrounding air, max

60 °C (140°F)

Relative humidity

IEC 60068-2-30 (Test Db, Unpackaged Damp Heat): 5…95%
noncondensing

Vibration

IEC 60068-2-6 (Test Fc, Operating): 2.5g @ 57…2000 Hz

Shock, operating

IEC 60068-2-27 (Test Ea, Unpackaged Shock): 30 g

Shock, nonoperating

IEC 60068-2-27 (Test Ea, Unpackaged Shock): 50 g

Emissions

CISPR 11: Group 1, Class A

ESD immunity

IEC 61000-4-2:
6 kV contact discharges
8 kV air discharges

Radiated RF immunity

IEC 61000-4-3:
10V/m with 1KHz sine-wave 80% AM from 80…2000 MHz
10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz
10V/m, with 200 Hz 50% Pulse 100% AM @ 1890 MHz
10V/m with 1KHz sine-wave 80% AM from 2000…2700 MHz

EFT/B immunity

IEC 61000-4-4:
±3 kV @ 5 kHz on communication ports

Surge transient immunity

IEC 61000-4-5:
±2 kV line-earth(CM) on communication ports

Conducted RF immunity

IEC 61000-4-6:
10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz