14 POINT I/O 2 and 4 Relay Output Modules

Publication 1734-IN055F-EN-E - March 2012

Wire the Module

Relay contacts are not directly powered by the internal power bus. Load power from the
internal power bus is available for the 1734-OW2 only. Connect to pins 6 and 7 for
V supply, and to pins 4 and 5 for V common.

WARNING: If you connect or disconnect wiring while the field-side power is
on, an electrical arc can occur. This could cause an explosion in hazardous
location installations. Be sure that power is removed or the area is
nonhazardous before proceeding.

Relay

Output

Module

Status

Network

Status

1734

OW4

NODE:

0

1

2

3

Relay

Output

Module

Status

Network

Status

1734

OW2

NODE:

0

1

Module status

Network status

Status of output 0
Status of output 1

C

V

C

V

C = Common

V = Supply

Output 0A

Output 0B

Output 1A

Output 1B

Status of output 2
Status of output 3

Output 0A

Output 0B

Output 1A

Output 1B

Output 2A

Output 2B

Output 3A

Output 3B