Rockwell Automation 1734-OW2_OW4, Series C Point I/O 2 and 4 Relay Output Modules User Manual

Page 19

Advertising
background image

POINT I/O 2 and 4 Relay Output Modules 19

Publication 1734-IN055F-EN-E - March 2012

Network
status

Off

Device is not online:

- Device has not completed dup_MAC-id test.

- Device not powered – check module status indicator.

Flashing green

Device is online but has no connections in the established
state.

Green

Device is online and has connections in the established
state.

Flashing red

One or more I/O connections are in timed-out state.

Red

Critical link failure – failed communication device. Device
detected error that prevents it from communicating on the
network.

Flashing
red/green

Communication faulted device – the device has detected a
network access error and is in communication faulted
state. Device has received and accepted an Identity
Communication Faulted Request – long protocol message.

I/O status

Off

Outputs off.

Yellow

Outputs on.

Indicator Status for Modules

Status

Description