Specifications – Rockwell Automation 1734-OW2_OW4, Series C Point I/O 2 and 4 Relay Output Modules User Manual

Page 20

Advertising
background image

20 POINT I/O 2 and 4 Relay Output Modules

Publication 1734-IN055F-EN-E - March 2012

Specifications

General Specifications

Attribute

Value

Outputs per module

1734-OW2 – 2 Form A isolated (normally open)
electromechanical relays

1734-OW4 – 4 Form A isolated (normally open)
electromechanical relays

Off-state leakage current, max

1.2 A @ 240V AC, and bleed resistor through
snubber circuit

Terminal base screw torque

Determined by installed terminal block

Power consumption

0.8 W

Power dissipation, max

0.5 W

Backplane power

5V DC, 80 mA

Contact rating

5…30V DC @ 2.0 A resistive

120V AC @ 2.0 A resistive

240V AC @ 2.0 A resistive

1800 VA make, 180 VA break

Isolation voltage

250V (continuous), Basic Insulation Type

Type tested @ 2550V DC for 60 s, field-side to system, and
between contact sets

Switching frequency, max

1 operation/3 s (0.3 Hz @ rated load)

Expected life of
electrical contacts, min

100,000 operations @ rated load

Wiring category

(1)

(1)

Use this conductor category information for planning conductor routing as described in Industrial Automation Wiring
and Grounding Guidelines, publication

1770-4.1

.

1 – on signal ports

Wire size

0.25…2.5 mm

2

(22…14 AWG) solid or stranded copper

wire rated at 75

°

C (167

°

F), or greater, 1.2 mm (3/64 in.)

insulation max

Enclosure type rating

None (open-style)

Pilot duty rating

R150

North American temp code

T4A

IEC temp code

T4

Advertising