Armorpoint i/o devicenet adapters 15 publication, Environmental specifications, General specifications – Rockwell Automation 1738-ADNX ArmorPoint DeviceNet Adapters, Series A User Manual

Page 15

Advertising
background image

ArmorPOINT I/O DeviceNet Adapters 15

Publication

1738-IN014D-EN-E - December 2010

Mounting base screw torque

M4 (#8) screw

0.86 Nm (7.5 lb-in) in Aluminum

1.81 Nm (16 lb-in) in Steel

Wiring category

(1)

1 – on power ports

1 – on communications ports

(1)

Use this Conductor Category information for planning conductor routing. Refer to publication

1770-4.1

,

Industrial Automation Wiring and Grounding Guidelines.

Environmental Specifications

Attribute

Value

Temperature, operating

IEC 60068-2-1 (Test Ad, Operating Cold),

IEC 60068-2-2 (Test Bd, Operating Dry Heat),

IEC 60068-2-14 (Test Nb, Operating Thermal Shock):

-20…60 °C (-4…140 °F)

Temperature, non-operating IEC 60068-2-1 (Test Ab, Unpackaged Non-operating Cold),

IEC 60068-2-2 (Test Bb, Unpackaged Non-operating Dry Heat),

IEC 60068-2-14 (Test Na, Unpackaged Non-operating Thermal Shock):

-40…85 °C (-40…185 °F)

Relative humidity

IEC 60068-2-30 (Test Db, Unpackaged Damp Heat):

5…95% non-condensing

Vibration

IEC60068-2-6 (Test Fc, Operating):

5 g @ 10…500 Hz

Shock, operating

IEC60068-2-27 (Test Ea, Unpackaged Shock):

30 g

Shock, non-operating

IEC60068-2-27 (Test Ea, Unpackaged Shock):

50 g

Emissions

CISPR 11:

Group 1, Class A

ESD immunity

IEC 61000-4-2:

6 kV contact discharges

8 kV air discharges

Radiated RF immunity

IEC 61000-4-3:

10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz

10V/m with 200 Hz 50% Pulse 100% AM @ 900 Mhz

10V/m with 200 Hz 50% Pulse 100% AM @ 1890 Mhz

3V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz

(1738-ADN12, 1738-ADN18 and 1738-ADN18P only)

General Specifications

Advertising