8 ArmorPOINT I/O DeviceNet Adapters

Publication

1738-IN014D-EN-E - December 2010

minor fault occurs, which is indicated by a flashing red Adapter Status LED.
Settings of 64…99 cause the module to use the last valid node address stored
internally. Example: The last setting internally was 40. If a change is made to
68, and then you power up, the address will default to 40.

The module is equipped with AutoBaud detect. AutoBaud lets the module
read the settings already in use on your DeviceNet network and automatically
adjusts to follow those settings.

Wire the Adapter

Follow the wiring instructions for the ArmorPOINT I/O

DeviceNet adapters.

1738-ADN12 and 1738-ADNX

1738-ADN18, 1738-ADN18P

(View into connector)

Pin 1 Drain

Pin 2 + V

Pin 3 - V

Pin 4 CAN_High

Pin 5 CAN_Low

Male in connector

43763

43764

Female out connector (1738-ADN12)

(Subnet out – 1738-ADNX only)

(View into connector)

Pin 1 Drain

Pin 2 + V

Pin 3 - V

Pin 4 CAN_High

Pin 5 CAN_Low

Male in connector

43746

43749

Female out connector

(1738-ADN18P only)