Remove the adapter from the mounting base, Set the network address – Rockwell Automation 1738-ADNX ArmorPoint DeviceNet Adapters, Series A User Manual

Page 7

Advertising
background image

ArmorPOINT I/O DeviceNet Adapters 7

Publication

1738-IN014D-EN-E - December 2010

Remove the Adapter From the Mounting Base

Follow the instructions to remove the adapter from the mounting base.

1. Put a flat blade screwdriver into the slot of the orange latching

mechanism.

2. Push the screwdriver toward the I/O module to disengage the latch.

The module lifts up off the base.

3. Pull the module off the base.

Set the Network Address

Valid node addresses are 00…63.

Set the node address using either the rotary switches, RSNetWorx for
DeviceNet, DeviceNetManager, or another software configuration tool.
Setting the switches at any number from 64…99 allows the software to have
address control.

Each module is shipped with the switches set for node address 63. Remove the
caps on the front of the module to access the switches. The two switches are:

• X10 (most significant digit) – left side of module

• X1 (least significant digit) – right side of module

Network Node Example

To reset the node address, use a small blade screwdriver to rotate the switches.
Line up the small notch on the switch with the number setting you wish to use
and then cycle power.

The I/O adapter periodically reads the rotary switches. If the switches have
changed since the last reading and they no longer match the online address, a

This example shows
the network address
set at 63.

44316