Connecting Power

The 1788-CN2FF requires 15-30V dc power and the cable is limited to a maximum of 3m in
length. One power supply can support several CN2FFs. The power connector is a 6-pin
screw terminal connector. The pinout for the power connector is shown in Figure 4.

Figure 4 Power Connector Pinout

Connect the primary power supply to the center V and C pair. An optional backup power
supply may be connected to the left V and C pair. The right V and C pair may be used to
chain the primary power supply to other devices. All three terminals labeled C are connected
in the CN2FF. The right two V terminals are connected in the CN2FF. These connections are
indicated on the power connector by the lines over the V and C terminals.

IMPORTANT

Make sure that the power to the network is off when
connecting the module.

v

v

v

c c

c

+

+

V

C

43170

15-30 V dc Backup
Power Supply
(optional)

15-30 V dc
Primary Power
Supply

To adjacent device
(optional connection)