22 ControlNet-to-Foundation Fieldbus H1 Linking Device

Publication 1788-IN051D-EN-P - February 2004

Specifications

Type

Specifications

Operating Temperature

0 to 60°C (32 to 140°F)
IEC 60068-2-1 (Test Ad, Operating Cold),
IEC 60068-2-2 (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal Shock)

Storage Temperature

–40 to 85°C (–40 to 185°F)
IEC 60068-2-1 (Test Ab, Un-packaged Non-operating Cold),
IEC 60068-2-2 (Test Bb, Un-packaged Non-operating Dry Heat),
IEC 60068-2-14 (Test Na, Un-packaged Non-operating Thermal Shock)

Relative Humidity

5 to 95% non-condensing

IEC 60068-2-30 (Test Db, Un-packaged Non-operating Damp Heat)

Vibration

IEC60068-2-6 (Test Fc, Operating): 2g @ 10-500Hz

Physical Dimensions

4.375 in. x 4.375 in x 4.5 in

• ControlNet connectors are on top of the unit

• Allow 1.5 inches for the connectors.

Shock

IEC60068-2-27 (Test Ea, Unpackaged shock):

Operating 30g
Non-operating 50g

Emissions

CISPR 11: Group 1, Class A

ESD Immunity

IEC 61000-4-2:

4kV contact discharges
8kV air discharges

Radiated RF Immunity

IEC 61000-4-3:

10V/m with 1kHz sine-wave 80%AM from 30MHz to 1000MHz
10V/m with 200Hz 50% Pulse 100%AM at 900Mhz

EFT/B Immunity

IEC 61000-4-4: ±2kV at 5kHz on signal ports

Surge Transient Immunity

IEC 61000-4-5: ±1kV line-line(DM) and ±2kV line-earth(CM) on signal ports

Conducted RF Immunity

IEC 61000-4-6: 10Vrms with 1kHz sine-wave 80%AM from 150kHz to 80MHz

Magnetic Field Immunity

IEC 61000-4-8: 30A/m at 50Hz

Enclosure Type Rating

None (open-style)

Communication

• ControlNet - redundant media

• NAP, network access port

• F

OUNDATION

Fieldbus H1, 2 independent channels

• LAS on both channels

• Time Master on both channels

Mounting

35 mm DIN rail

Power Requirements

Class 2 power supply 24V dc
15-30V dc
270 mA @ 24V dc (typical)