Interpreting the leds: controlnet network status – Rockwell Automation 1788-CN2FF ControlNet to Foundation Fieldbus H1 Linking Device Installation Instructions User Manual

Page 15

Advertising
background image

ControlNet-to-Foundation Fieldbus H1 Linking Device 15

Publication 1788-IN051D-EN-P - February 2004

Interpreting the LEDs: ControlNet Network Status

The ControlNet network status LEDs are located on the front of the 1788-CN2FF, beside
the ControlNet BNC connectors, as shown in Figure 1, Item 3. They indicate the state of the
ControlNet connected to the BNC connectors. These LEDs do not reflect anything about
the status of the network access port (NAP). If more than one state is present, the LEDs
always reflect the highest priority status present on the network. Table 7 describes the LED
states and the priority of each status.

Table 7 ControlNet Network LED Status Descriptions

LED State

Priority

How to View

Cause

Both steady off

1 (highest)

View together

Reset or no power

Both steady red

2

Failed to link interface to ControlNet

Alternating red & green

3

Self testing

Alternating red

4

Bad node configuration (such as duplicate
ControlNet network address)

Steady off

5

View
independently

Channel disabled or not supported

Flashing red & green

6

Invalid link configuration

Flashing red

7

Link fault or no frames received

Flashing green

8

Temporary channel error or listen only

Steady green

9 (lowest)

Normal operation