Communicate with your module – Rockwell Automation 1738-IB16DM12 ArmorPoint 24V DC 16 Point Input and Output Modules  User Manual

Page 10

Advertising
background image

10 ArmorPoint 24V DC 16 Point Input and Output Modules, Series A

Publication

1738-IN023B-EN-E - February 2010

1738-IB16DM12

Communicate with Your Module

I/O messages are sent to (consumed) and received from (produced) the
ArmorPoint I/O modules. Messages are mapped into the processor’s
memory. ArmorPoint I/O output modules produce 1 byte of input data
(scanner Rx - status). They consume 2 Bytes of I/O data (scanner Tx).
ArmorPoint I/O input modules produce 2 or 3 bytes of input data (scanner
Rx - status). They do not consume I/O data (scanner Tx).

ATTENTION

Make sure all connectors and caps are securely tightened to properly seal the
connections against leaks and maintain IP enclosure type requirements.

(view into connector)

Pin 1 - SSV 0 (M12-A,B)

SSV 1 (M12-C,D)

SSV 2 (M12-E,F)

SSV 3 (M12-G,H)

Pin 2 - 24V DC input 1 (M12-A)

24V DC input 3 (M12-B)

24V DC input 5 (M12-C)

24V DC input 7 (M12-D)

24V DC input 9 (M12-E)

24V DC input 11 (M12-F)

24V DC input 13 (M12-G)

24V DC input 15 (M12-H)

Pin 3 -Common

Pin 4 - 24V DC input 0 (M12-A)

24V DC input 2 (M12-B)

24V DC input 4 (M12-C)

24V DC input 6 (M12-D)

24V DC input 8 (M12-E)

24V DC input 10 (M12-F)

24V DC input 12 (M12-G)

24V DC input 14 (M12-H)

Pin 5 - Not Used

43664

Advertising