Rockwell Automation 1738-IB16DM12 ArmorPoint 24V DC 16 Point Input and Output Modules  User Manual

Page 17

Advertising
background image

ArmorPoint 24V DC 16 Point Input and Output Modules, Series A 17

Publication

1738-IN023B-EN-E - February 2010

Environmental Specifications

Attribute

Value

Temperature, operating

IEC 60068-2-1 (Test Ad, Operating Cold),

IEC 60068-2-2 (Test Bd, Operating Dry Heat),

IEC 60068-2-14 (Test Nb, Operating Thermal Shock):

-20…60 °C (-4…140 °F)

Temperature, storage

IEC 60068-2-1 (Test Ab, unpackaged nonoperating cold),

IEC 60068-2-2 (Test Bb, unpackaged nonoperating dry heat):
-40…85 °C (-40…185 °F)

Relative humidity

IEC 60068-2-30 (Test Db, Unpackaged Damp Heat):

5…95% non-condensing

Shock, operating

IEC 60068-2-27 (Test Ea, Unpackaged Shock): 30g

Shock, non-operating

IEC 60068-2-27 (Test Ea, Unpackaged Shock): 50g

Vibration

IEC 60068-2-6 (Test Fc, Operating): 5g @ 10...500 Hz

Emissions

CISPR 11: Group 1, Class A

ESD immunity

IEC 61000-4-2:

6 kV contact discharges

8 kV air discharges

Radiated RF immunity

IEC 61000-4-3:

10V/m with 1 kHz sine-wave 80%AM from 80…2000 MHz

10V/m with 200 Hz 50% Pulse 100%AM at 900 MHz

10V/m with 200 Hz 50% Pulse 100%AM at 1890 MHz

3V/m with 1 kHz sine-wave 80%AM from 2000...2700 MHz

EFT/B immunity

IEC 61000-4-4:

±3kV at 5 kHz on signal ports

Surge transient
immunity

IEC 61000-4-5:

±1 kV line-line (DM) and ±2 kV line-earth (CM) on signal ports

Conducted RF
immunity

IEC 61000-4-6:

10V rms with 1 kHz sine-wave 80%AM from 150 kHz...80 MHz