Rockwell Automation 1738-IB16DM12 ArmorPoint 24V DC 16 Point Input and Output Modules  User Manual

Page 16

Advertising
background image

16 ArmorPoint 24V DC 16 Point Input and Output Modules, Series A

Publication

1738-IN023B-EN-E - February 2010

General Specifications

Attribute

Value

Power dissipation

1738-OB16E19M23, 1738-OB16EM12, 1738-OB16E25DS –

3.0W @ 28.8V DC

1738-IB16DM12 – 2.7W @ 28.8V DC maximum

Thermal dissipation

1738-OB16E19M23, 1738-OB16EM12, 1738-OB16E25DS –

10.3 BTU/hr @ 28.8V DC

1738-IB16DM12 – 9.2 BTU/hr @ 28.8V DC maximum

Isolation voltage

50V (continuous), Reinforced Insulation Type, field-side to system

Type tested at 1000V DC for 60 s, field-side to system

No isolation between individual channels

Dimensions (HxWxD),
approx.

120 x 72 x 42 mm

4.72 x 2.83 x 4.25 in

including I/O and mounting base

Weight

290 g (10.24 oz)

LED indicators

16 yellow input/output status, logic side

1 green/red network status, logic side

1 green/red module status, logic side

1 red fault status, logic side

PointBus current

1738-OB16E19M23, 1738-OB16EM12, 1738-OB16E25DS –

150 mA @ 5V DC maximum

1738-IB16DM12 – 75 mA @ 5V DC maximum

Wiring category

(1)

1 - on signal ports

Keyswitch position

1

Enclosure type rating

Meets IP65/66/67/69K (when marked)

Mounting base screw
torque

#8 screw

0.85 Nm (7.5 lb-in) in Aluminum

1.81 Nm (16 lb-in) in Steel

(1)

Use this Conductor Category information for planning conductor routing. Refer to Publication

1770-4.1

,

Industrial Automation Wiring and Grounding Guidelines.

Advertising