Counter configuration – Rockwell Automation 1738-IJM23 ArmorPOINT I/O 5V DC Encoder/Counter Modules, Series A User Manual

Page 10

Advertising
background image

Publication 1738-IN012B-EN-E - August 2013

10 ArmorPOINT I/O 5V DC Encoder/Counter Module, Series A

Counter Configuration

07 06 05 04 03 02 01 00

ZI

MD

CF

Counter 0

0

0

0

0

Counter

0

0

0

1

Encoder X1

0

0

1

0

Encoder X2

0

0

1

1

Not used

0

1

0

0

Encoder X4

0

1

0

1

Period/Rate

0

1

1

0

Not used

0

1

1

1

Rate Measurement

0

0

0

Store Count Disabled

0

0

1

Mode 1 - store/continue

0

1

0

Mode 2 - store/wait/resume

0

1

1

Mode 3 - store, reset/wait/start

1

0

0

Mode 4 - store, reset/start

1

0

1

Reserved

1

1

0

Reserved

1

1

1

Reserved

0

Z input - 0 = not inverted

1

Z input - 1 = inverted

Advertising