14 ArmorPOINT I/O 5V DC Encoder/Counter Module, Series A

Indication

Probable Cause

Network Status

Off

Device is not online:

– Device has not completed dup_MAC-id test.

– Device not powered. Check module status indicator.

Flashing Green

Device is online but has no connections in the established state.

Green

Device is online and has connections in the established state.

Flashing Red

One or more I/O connections in timed-out state.

Red

Critical link failure – failed communication device. Device
detected error that prevents it from communicating on the
network.

Flashing Red/Green

Communication faulted device – the device has detected a
network access error and is in communication faulted state.
Device has received and accepted an Identity Communication
Faulted Request – long protocol message.

Indication

Probable Cause

I/O Status

Input Status

Off

Input inactive

Yellow

Input is active and under control

Flashing Yellow

Input is toggling