Troubleshooting With the Status Indicators and Status Display

The module has indicators on the front panel as shown below. These indicators
consist of:

health indicators

status indicators

display of status and address

Use these indicators to troubleshoot the module.

The following tables describe how to use the indicators to troubleshoot your
module.

Health Indicators and Display Mnemonics

OK LED

Display

Description

Probable Cause

Recommended Action

Off

None

Module is not
communicating.

Power supply fault.

Check power supply, and
seat adapter firmly in
chassis.

Off

None

Module is not
communicating.

Defective adapter.

Replace adapter.

Off

POST

Adapter is running
Power On Self Test.

None

None

Amber

0000 through
9999

Adapter is running
Power On Self Test.

None

None

Amber

A/A

Adapter is
displaying Series
and Revision level.

None

None

ADDRESS/STATUS

ADDRESS/STATUS

B

A

A

A

A

B

OK

OK

Status Display and Net
Address

Health Indicators ControlNet
Status Indicators

1747-ACN15

1747-ACNR15