Connecting your adapter to the controlnet network – Rockwell Automation 1747-ACNR15 ControlNet Adapter Module Installation Instructions User Manual

Page 9

Advertising
background image

ControlNet Adapter Module 9

Publication 1747-IN017C-EN-P - May 2001

Connecting Your Adapter to the ControlNet Network

Connect your 1747-ACN15 or -ACNR15 adapter module to a ControlNet network via
taps. as shown below:

1. Remove the tap’s dust cap (located on the straight or right angle connector).

IMPORTANT

Taps contain passive electronics and must be purchased from
Rockwell Automation for the network to function properly.

If your node supports:

Connect the tap’s straight or right angle connector:

Non-redundant media

to the channel A connector on the 1747-ACN15 or 1747-ACNR15
(channel B on the 1747-ACNR15 is not used)

(1)

(1)

While both channels are active, we recommend using channel A for non-redundant media.

Redundant media

from trunkline A to channel A on the 1747-ACNR15

from trunkline B to channel B on the 1747-ACNR15

ATTENTION

!

Do not allow any metal portions of the tap to contact any
conductive material. If you disconnect the tap from the
adapter, place the dust cap back on the straight or right angle
connector to prevent the connector from accidentally
contacting a metallic grounded surface.

Straight T-tap

Straight Y-tap

Right-angle T-tap

Right-angle Y-tap

1766-TPS

1786-TPYS

1786-TPR

1786-TPYR

segment 1

Tap

dust cap