ControlNet Status Indicators

steady - indicator is on continuously in the defined state.

alternating - the two indicators alternate between the two defined states at
the same time (applies to both indicators viewed together). The two
indicators are always in opposite states, out of phase.

flashing - the indicator alternates between the two defined states (applies to
each indicator viewed independent of the other). If both indicators are
flashing, they must flash together, in phase.

Cause

Action

Off

No power

None or power up

Steady red

Faulted unit

Cycle power
If fault persists, contact Technical Support at
440.646.6800.

Alternating
red/green

Self-test

None

Alternating red/off

Incorrect node configuration

Check network address and other ControlNet
configuration parameters

Cause

Action

Off

Channel disabled

Program network for redundant media, if required

Steady green

Normal operation

None

Flashing green/off

Temporary errors

None; unit will self-correct

Listen only

Cycle power

Flashing red/off

Media fault

Check media for broken cables, loose connectors,

missing terminators, etc.

No other nodes present on
network

Add other nodes to the network

Flashing red/green

Incorrect network
configuration

Cycle power or reset unit
If fault persists, contact Technical Support at
440.646-6800.