Switch bank 0 – Rockwell Automation 1771-DCM USER MANUAL 1771-DCM User Manual

Page 10

Advertising
background image

Selecting Options

Chapter 3

3Ć2

Each switch bank has eight switches. Set each switch to the ON (closed)
position by depressing the right-hand side of the switch or to the OFF
(open) position by depressing the left-hand side of the switch (Figure 3.2).

Figure 3.2

Example Switch Bank

1

OPEN

2
3
4
5
6
7
8

Switches 1 and 3 are OFF (open)

Shading represents the switch position

12826

The options that you select with Switch Bank 0 are as follows:

Switch 1 Ć Baud Rate

ON (Closed) for 57.6K Baud
OFF (Open) for 115.2K Baud

Set the baud rate equal to that of the scanner of your supervisory
processor. You can transmit data up to 10,000 feet at a data rate of
57.6K baud or up to 5,000 feet at a data rate of 115.2K baud.

Switch 2 Ć Not Used

Switch Bank 0