1771-dcm switch settings, Supervisory processor logic – Rockwell Automation 1771-DCM USER MANUAL 1771-DCM User Manual

Page 24

Advertising
background image

Programming the 1771-DCM

Chapter 6

6Ć3

Figure 6.2

Local Processor Programming Example (PLC-5)

BTR

ENABLE BIT

Rung 2:0

PLC5 local write rung. The DCM is located in the same I/O chassis as the PLC5, and is set for block transfer. The local procesĆ

sor's write length must match the supervisory processor's read length.

N12:0

15

N12:5

15

BTW

ENABLE BIT

BTR

ENABLE BIT

N12:0

15

N12:5

15

BTW

ENABLE BIT

Rung 2:1

PLC5 local read rung. The DCM is located in the same I/O chassis as the PLC5, and is set for block transfer. The local procesĆ

sor's read length must match the supervisory processor's write length.

EN

BTW
BLOCK TRNSFR WRITE
Rack
Group
Module
Control Block

0
3
1

N12:5

DN

Data file
Length
Continuous

N13:30

17

N

ER

EN

BTR
BLOCK TRNSFR READ
Rack
Group
Module
Control Block

0
3
1

N12:0

DN

Data file
Length
Continuous

N13:30

21

N

ER

Select module operating conditions by setting switches on the module for
discrete data transfer or block transfer as follows:

Discrete Data Transfer

Block Transfer

Transfer Method

Transfer Method

Rack Size

Data Protect (If Applicable)

Set other switches as required by your application.

The addresses that you use for the 1771–DCM in the supervisory
processor’s ladder program are the addresses (RGS) to which you
configure your 1771–DCM using Switch Banks 0 and 1:

I/O Rack Number (Switch Bank 1, Switches 1 through 6).

1771-DCM Switch Settings

Supervisory Processor Logic