Overview of Direct

Communication Module

Chapter 2

2Ć3

Baud Rate/Distance

Select the communication rate and distance to the supervisory procesĆ

sor as either 57.6K baud to a distance of 10,000 feet, or 115.2K baud

to a distance of 5,000 feet.

Transfer Method

Select block transfer or discrete data transfer between the 1771ĆDCM

and the supervisory processor.

Rack Size

When using discrete data transfer, select the number of slots that deĆ

termines how the 1771ĆDCM appears to the scanner of the supervisoĆ

ry processor (the size of the I/O chassis simulated by the 1771ĆDCM).

This also determines the number of words transferred.

Protected Data

Select protected data to prevent block transfers from the local procesĆ

sor until the supervisory processor has received the previous block

transfer.

I/O Rack Address

Designate the I/O rack number, the number of the first module group

of the I/O chassis simulated by the 1771ĆDCM, and whether it has the

highest starting module group address of two or more chassis asĆ

signed to the same rack address.

These options are described in Chapter 3.

You can use the 1771-DCM in a variety of applications where the transfer
of data table values is required. For example, consider using it to:

Call messages stored in the data table of the supervisory processor and

outputted through an ASCII I/O module (cat. no. 1771-DA) or BASIC
module (cat. no. 1771-DB)

Download recipe data table values from supervisory to local

processor(s) where you want local processor(s) to execute different
versions of the same program

Download commands from the supervisory processor to execute

different sections of a ladder diagram program at the local processor

Use the 1771-DCM with any Allen-Bradley programmable controller that
uses block transfer and the 1771 I/O structure.

Reserve an I/O slot for this module by placing keying bands on the
backplane connector. Position keying bands between the following
numbers labeled on the backplane adjacent to the upper backplane
connector. The keying bands mate with corresponding slots in the module
connector:

Between 2 and 4
Between 16 and 18

Example Applications

Compatible Processors

Keying