Trunkline/dropline hookup, Connecting cables chapter 4 – Rockwell Automation 1771-DCM USER MANUAL 1771-DCM User Manual

Page 17

Advertising
background image

Connecting Cables

Chapter 4

4Ć3

When using the trunkline/dropline hookup, connect the 1771–DCM to the
serial I/O channel trunkline using a dropline that does not exceed 100 feet
in length (Figure 4.3). Connect the dropline to the trunkline using a T
connector (cat. no. 1770–XG) or a station connector (cat. no. 1770–SC).
There are no restrictions as to the spacing between station connectors or T
connectors if you do not exceed the maximum cable distance. Terminate
the open port at the first and last T connector or station connector using a
Terminator Set (cat. no. 1770–XF).

Figure 4.3

Example Trunkline/Dropline Hookup with T Connectors

PLC -2/30

1772 -SD2

Bl ue

Shield

Clear

1
2
3

Clear

Shield

Blue

2

1
2

1771 -ASB

1

2

Blue

Shield

Clear

1

Remote I/O Chassis

1771 -ASB

1771 -DCM

1771 -DCM

1771 -ASB

Install Terminator Resistor

(cat. no. 1770ĆXF)

12662

1

1

1

Trunkline/Dropline Hookup