8 - troubleshooting your 1771-dcm, Troubleshooting your 1771-dcm, Led display – Rockwell Automation 1771-DCM USER MANUAL 1771-DCM User Manual

Page 48: Led display for fault conditions

Advertising
background image

Chapter

8

8Ć1

Troubleshooting Your 1771-DCM

When troubleshooting your 1771–DCM, check each of the following
sources in the order given for the cause of the fault:

LEDs on the 1771–DCM
Block transfer rungs in the ladder program of your local or supervisory

processor

Status bits in the status word read by the local or supervisory processor

Under normal operating conditions, the LEDs are lit as follows:

Power (PWR)

ON

Serial Communication (SER COM)

ON

Backplane Communications

(BCKPLN COM)

ON

Module Fault (DCM FLT)

OFF

If a fault should occur, the LED display changes to indicate the source of
the fault which you diagnose as follows:

LED

Status

Diagnosis

PWR

OFF

The 1771-DCM is not getting +5V DC. Check the backplane

power supply.

SER COM

Blinking

Supervisory processor is in program or test mode. Check mode

selection.

Supervisory processor is not connected to the scanner. Check

the cable between processor and scanner (PLC-2/30 procesĆ

sor).

Supervisory processor detected a fault and turned off outputs.

Check processor LEDs and status of outputs.

OFF

The supervisory processor is not communicating with the

1771-DCM. Check cable connections in the remote I/O link to

the 1771-DCM.

Troubleshooting Your 1771-DCM

LED Display for Normal

Operation

LED Display for Fault Conditions