Installing your module – Rockwell Automation 1771-OND INSTL.INSTR AC (24V) OUTPT.MOD User Manual

Page 3

Advertising
background image

AC (24V) Output Module

3

Publication 1771Ć5.41 - May 1996

In this section we tell you how to set the fault mode selection plug,
key your I/O chassis, install your module and make your wiring
connections.

Fault Mode Selection

You may select one of two output-failure configurations (last state or
reset) by positioning a configuration plug on the bottom edge of the
printed circuit board. This configuration plug is independent of the
last state switch on the I/O chassis backplane.

To set the fault mode selection, proceed as follows:

1. Locate the fault mode selection plug at the bottom edge of the

module circuit board (Figure 1).

Figure 1

Fault Mode Selection Plug

LS

RESET

Fault Mode Selection Plug

Bottom edge of circuit board

(shown in last state position)

10673-I

2. Using your finger, slide the plug off the two posts.,

3. Carefully position the plug on two of the three posts that

correspond to your requirement.

Keying Your I/O Chassis

Use the plastic keying bands, shipped with each I/O chassis, to key
the I/O slots to accept only this type of module.

The module circuit board is slotted in two places on the rear edge.
The position of the keying bands on the backplane connector must
correspond to these slots to allow insertion of the module. You can
key any connector in an I/O chassis to receive this module except for
the left-most connector reserved for adapter or processor modules.
Place keying bands between the following numbers labeled on the
backplane connector:

Between 20 and 22

Between 32 and 34

You can change the position of these keys if system redesign and
rewiring makes insertion of a different module necessary.

Installing Your Module