AC (24V) Output Module

6

Publication 1771Ć5.41 - May 1996

Important: You can use an AC (24V) Output Module (cat. no.

1771-OND) to directly drive terminals on an AC (24V)
Input Module (cat. no. 1771-IND) (Figure 3). You can
also use a 1771-OND Output module to drive an AC
(24V) Input Module (cat. no. 1771-IN) but you must
connect a 250 ohm, 5W resistor between the output
terminal and L2 (common) as shown in Figure 3. Use
the same ac power source to power both modules to
ensure proper phasing and prevent module damage.

Figure 3

Driving an Input Module with an Output Module

Note: 1771ĆOND output voltage

range is 10Ć60V ac. However, the

onĆstate voltage range of the

1771ĆIND is 19Ć29V ac.

L1

24V ac High

L2

ac Low

(Cat. No. 1771ĆIN)

Note: 1771ĆOND output voltage

range is 10Ć60V ac. However, the

onĆstate voltage range of the

1771ĆIN is 12Ć28V ac.

L2

ac Low

250 ohm 5W

resistor

L1

24V ac High

L2

AC (24V)

Input Module

AC (24V)

Output Module

(Cat. No. 1771ĆOND)

AC (24V)

Input Module

(Cat. No. 1771ĆIND)

AC (24V)

Output Module

(Cat. No. 1771ĆOND)