Connecting Wiring to the Output Module

Connections to the output module are made to the field wiring arm
(cat. no. 1771-WH) shipped with the module. An optional fused
wiring arm is available (cat. no. 1771-WHF) which provides
individual fusing for each circuit. Attach the wiring arm to the pivot
bar on the bottom of the I/O chassis. The wiring arm pivots upward
and connects with the module so you can install or remove the
module without disconnecting the wires.

You must supply ac (L1) at terminals A through D on the wiring
arm. You need four ac connections to accommodate the total
required surge rating on the module without overstressing any single
connection on the field wiring arm. Jumper all ac (L1) connections
together to prevent module damage.

Figure 2

Connection Diagram

Terminal A

Terminal B

Terminal C

Terminal D

(Actual wiring runs in this direction.)

Terminal E

L1

24V ac

ac Low

Output 00

Output 01

Output 02

Output 03

Output 04

Output 05

Output 06

Output 07

Output 10

Output 11

Output 12

Output 13

Output 14

Output 15

Output 16

Output 17

L2

Output

Device

A
B
C
D
00
01
02
03
04
05
06
07
10
11
12
13
14
15
16
17
E

10674ĆI