6 installation of fiber optics, Installation of fiber optics, 6installation of fiber optics – Metrohm NIRS XDS Process Analyzer – DirectLight/NonContact User Manual

Page 39

Advertising
background image

▪▪▪▪▪▪▪

37

6

Installation of Fiber Optics

Fiber optic cables are quite rugged, and are jacketed to protect the delicate optical fibers within.
While protected, the fiber bundles are still somewhat fragile when not handled correctly. Always use
care when routing and installing fibers.

The fibers are installed on the instrument, and are shipped in a
coiled position in the shipping container.

Handle very gently when moving and lifting, to avoid damage.
Follow these guidelines:

1.

Never bend in a radius of less than 6” (153mm).

2.

Never pull on the fiber bundle, as this can stress the fiber and cause breakage of individual

strands.

3.

Avoid any impact or abuse of the fiber bundles.

4.

Do not leave the fiber optic cable unsupported. Any motion in the cable during scanning may

cause minor variations in spectral response, due to slight differences in the internal reflection
at different bend angles. While this effect is quite small, it can cause the error of prediction to
increase slightly.

5.

Never scratch or mar the polished ends of the fibers.

Cable Tray:

Due to the intrinsic safety and resistance to inductance of the
fiber bundles, these fibers can be installed in commercially
available cable trays. This method of fiber installation is
preferable due to the fact that the fiber is not exposed to a
constrictive environment, as is the case with conduit.
Therefore, it is less likely that an individual fiber will break
when being installed in a cable tray.

The fiber may be installed in a “ladder tray” with supports every 4-6 inches (100-

150mm). Note the minimum fiber bend radius as mentioned above. A solid-bottom tray may also be
used. Tray material may be metal, fiberglass, or any other material that does not react with the
jacketing material.

Advertising