Inspect the incoming water line for check valves or water pressure reducing

valves. Any type of check valve may cause pressure to build up in the heater and

cause tank failure. If the heater is installed in a closed system or if backflow pre-

venters and pressure regulators are installed, add an expansion tank. Do not try

to heat hard water. Install a water softener if the heater is being used in a hard

water area (water hardness more than 7 grains).

An approved temperature and pressure (T&P) relief valve is factory installed in

the opening provided in the upper right hand side of the heater. Pipe the T&P to

within 6" of the floor or to a floor drain with a free flowing drain pipe. Do not install

a check valve in the cold water line.

Using “L” or “A” type venting, connect the heater to the chimney. Use the same

size smoke pipe as the heater flue pipe (on models 20e, 20pp, 32E, 32PP and

33E, you may use 4" with a reducer if needed).

WARNING: On Models 40E, 5OES, 50ESC, 51E, 51EC, 51PP, 51PPC. 71E and

120E, do not reduce the smoke pipe diameter. Run a separate smoke pipe from

the water heater to the chimney wherever possible.

If it is necessary to tee into an existing smoke pipe, be sure the connector being

teed into is large enough to accommodate the products of combustion of all units

attached to it. When teeing into another connector, run in at 45° angle (see Figure

1). Install a draft regulator control only if necessary. Overfire draft should not be

positive. Stack draft should be -.02” W.C. minimum to -.05” W.C. maximum; CO2

should be a minimum of 11%. If a draft control is installed on the chimney,

another one on the heater is not needed.

The oil burner is equipped with a primary relay. An aquastat with immersion

well is packed with the burner. The thermostat is factory set at 120°F for residen-

tial use (see caution on page 1 regarding temperature variations). Install the

immersion well with the aquastat and check the bulb length (see “Burner &

Controls” section, page 10).

Remove the cardboard core from the burner opening. Mount the burner on stud

bolts and place the gasket (supplied) between the burner flange and the heater.

Secure the burner to the heater with 1/4 -20 nuts (supplied). Open the inspection

door on the heater and check the burner tube with a mirror before firing to

be sure the opening is not blocked (see Maintenance and Service sections on

pages 6 and 7 for troubleshooting).

All wiring must comply with applicable codes and ordinances. The primary relay

is wired to the burner at the factory. Install the aquastat well in the 3/4" tapping at

the front of the heater. Be sure the sensing bulb is inserted all the way into the

well. For Honeywell aquastats, tighten the screw on top of the aquastat to secure

the control to the well. For Carlin EZ-Temp aquastats, refer to the pre-packaged

installation guide for proper set-up procedure. Refer to drawings for correct mod-

els. Connect the power supply to the aquastat and run through a fused discon-

nect switch (attached to heater in field). See Figure 1.

Gravity System: The oil burner is normally equipped with a single-stage pump

equipped for one line (gravity) flow. Use 1/2" O.D. soft copper tubing and attach

with flared fittings. DO NOT USE COMPRESSION FITTINGS. Install the shut

off valve and oil filter in the oil line. Follow the pump manufacturer’s instructions

(attached to the pump).

Lift System: The burner should be ordered with a 2-stage pump. Run a 2-line

system (suction and

return lines). Install the bypass plug according to the

instructions attached to pump (plug is in a bag with an instruction sheet).

CONNECT THE OIL

LINE

WARNING!! WHEN YOU

INSTALL THE BYPASS

PLUG YOU MUST RUN A

TWO-LINE SYSTEM.

CONNECT THE

ELECTRICITY

MOUNT THE OIL

BURNER

CONNECT TO

CHIMNEY