SERVICE

1. Check the fuel supply, electrical wiring and fuses, and make sure temperature

control is calling for heat.

2. If the motor runs but there is no flame, remove the electrode assembly, clean,

readjust to the burner manufacturer’s specifications, check the electrode porce-

lain for cracks and replace if necessary. Check the transformer to see if it is pro-

ducing a strong spark. (Use extreme CAUTION: The transformer has a 10,000

volt output). Check that the coupling between the motor and pump shaft is not

slipping. Check the set screw on the blower wheel for tightness. Clean or replace

the nozzle with the correct size and spray angle (see Chart A, page 11).

3. Bleed the pump and check for clear, air-free oil. If the oil is milky or frothy, check

the line for air leaks at fittings. Tighten all fittings again. Check the filter gaskets

and make sure cartridge is clean.

4. If the burner motor does not run, check the motor thermal overload button (red

button on end of motor). Reset the primary control by pushing the reset button on

the control. If the burner motor still does not run after resetting the control, turn off

the electricity and replace the flame detector (with the same make) located in the

burner compartment. Reset the primary control. If the motor still

does not run, replace the control.

5. If the burner ignites and runs a short time (30-40 seconds), then goes out on

safety, replace the flame detector. If the burner still runs only a short time, replace

the control.

6. If there is a smell of oil or combustion products, remove and clean the electrode

assembly (see No. 2 above). Check the draft in the stack above the heater. Stack

draft (pull in) should be -.02” W.C. minimum to -.05” W.C. maximum.

Check for exhaust fans in the heater room or adjacent areas which draw com-

bustion air away from heater. THE HEATER MUST HAVE COMBUSTION AIR TO

OPERATE.

For more information, contact your installer, the nearest Bock distributor, or write,

call or fax:

BOCK WATER HEATERS, INC.

110 South Dickinson Street, Madison, WI 53703

Phone: 608/257-2225 • Fax: 608/257-5304

Advertising