Bock Water heaters 32E User Manual

Page 5

Advertising
background image

– 5 –

PLACE THE

WATER

SYSTEM IN

OPERATION

Warning: Handhole

cover may loosen

during shipping –

check for tightness

before putting heater

in operation.

For any horizontal run exceeding the maximum length specified in Figure 4, or

any lift of more than 10 feet, a booster pump must be used. Booster pumps may

be obtained from Sun Tec Hydraulics, Rockford, Illinois. Booster pumps must be

installed as close to the oil supply tank as possible. Suction and return lines

should be the same diameter and both go within 6” of the bottom of the tank. The

return line should stop slightly above the suction line. Use a minimum of fittings.

Make bends in the tubing with as large a radius as possible. DO NOT USE COM-

PRESSION FITTINGS. Caution must be used in the final connection to the burner

so as not to strain the fuel unit. Before attaching the tubing to the burner, form a

coil in the tubing to minimize any vibration. Bury the oil lines in the floor for quiet

operation, making sure there are NO CONNECTIONS OR FITTINGS UNDER

THE FLOOR.

1. Fill the tank with water, opening a hot water faucet to allow trapped air to

escape from the heater. Open the cold water inlet valve. Shut off each faucet as

it delivers water that is free of air. Inspect for leaks. Never operate an empty or

partially full heater.

2. Be sure the oil tank is filled with #1 or #2 heating oil. Remove the transformer

hold down screw and swing the transformer back open on the hinge. Rotate the

blower wheel a few times to loosen the pump shaft. Swing the transformer closed

and fasten.

3. Bleed air from the oil line by opening the bleed valve on the fuel pump. Attach

a small plastic tube to the bleed valve fitting on the pump and run to a gallon

container. Turn on the electricity and set the thermostat so the burner motor runs.

The heater will not ignite when the bleed valve is open. Bleed the line until the oil

is completely clear, not milky or opaque. The oil must be transparent and free of

air bubbles and froth. To keep the burner control from locking out while bleeding

the pump, attach a jumper between the flame detector terminals after starting the

burner. Remove the jumper when finished. Shut the bleed valve and the burner

will ignite. Remove the plastic tubing. Set the pump pressure to 100 PSI for

Wayne, Carlin and Beckett burners and 150 PSI for Riello burners.

4. Adjust the burner combustion air in accordance with the burner manufacturer’s

instructions. Using combustion instruments, check the C02 and smoke. The C02

should be at least 10 1/2% minimum with 0-to-trace smoke on the Bacharach

scale.

Your log (or one similar to this) must be filled out as follows:

Date Time Test person’s name Set temp. oF

Outlet temp. oF

FIGURE 4: MAXIMUM LIFT & HORIZONTAL RUN

1-Pipe Single Stage Horizontal 2-Pipe Two-Stage Horizontal

System Pump Run System Pump Run

3/8” O.D. 1/2” O.D. 3/8” O.D. 1/2” O.D.

Lift Tube

Tube

Lift Tube Tube

0’

65’

100’

0’

75’

100’

4’

45’

100’

4’

64’

100’

7’

31’

100’

7’

55’

100’

8’

16’

64’

10’

47’

100’