– 6 –

5. While the burner is operating, disconnect one of the yellow cad cell wires.

Check to see that the burner control locks out in the time specified on the control.

Reattach the wire and reset the control. The burner should restart. Note: You may

have to wait a minute before resetting the control.

6. The thermostat is factory set at 120°F for residential use. (See caution on page

1 regarding temperature variations. It is the responsibility of the homeowner and

installer to verify that the installer follows the recommended quantitative testing

for measuring the outcoming water temperature. To make sure that the system

works properly after installation and in the future, it is recommended that the

heater’s performance be measured and monitored. Run water out of the tap near-

est the heater until it comes out warm. Using a calibrated thermometer, take a

measurement. If the water is not at a suitable temperature for the installation,

have a qualified service person adjust the aquastat. Contact Bock for further

information on the thermometer if needed.

WARNING: Hydrogen gas can be produced in a hot water system served by

a heater that has not been used for a long period of time (generally two

weeks or more.) Hydrogen gas is extremely flammable. To reduce the risk

of injury, open the hot water faucet at the highest location in the house for

several minutes before using any electrical appliance connected to the hot

water system. If hydrogen is present, there may be an unusual sound such

as air escaping through the pipe as the water begins to flow. Do not smoke

or allow an open flame near the faucet at the time it is open.

1. Oil the burner motor (5-10 drops) with #10 SAE motor oil (if applicable).

2. Install a new burner nozzle of the correct rate and angle. (See Chart A, page 11).

3. Clean and adjust the electrodes and inspect for cracks in the porcelain. Check

for corrosion on the buss bars and ignitor terminals.

4. Change the fuel oil filter and have the oil tank checked for sediment. Clean the

tank if necessary.

5. Keep the oil tank full to prevent water vapor from collecting inside the tank,

especially during the summer.

6. Check the smoke pipe and chimney. Clean and repair if necessary.

7. EVERY SIX to 12 MONTHS. Drain water from the heater tank and inspect for

sediment or lime accumulation. Flush out if necessary. If lime has accumulated,

remove with a commercial compound for dissolving lime or by scraping through

the hand hole opening (if supplied). Check water softening equipment if lime is

found in the tank. DO NOT ATTEMPT TO HEAT HARD WATER. (See mainte-

nance label on heater.)

8. Change the magnesium anode rods every six to 12 months or when they

are reduced to 3/8” diameter (see maintenance label on heater). We recom-

mend the installer use PermaBond LH-050. Teflon tape should not be used when

installing magnesium or aluminum anode rods.

9. Open the relief valve test lever to flush out the tank. Make sure it reseats itself.

10. If the heater is to be shut off in cold weather, drain the tank to prevent freezing.

MAINTENANCE

MEASURING THE

OUTCOMING

WATER

TEMPERATURE

Have the oil burner

serviced once each

year by a qualified

oil burner service

person. Service

should comply with

the burner manufac-

turer’s recommenda-

tions and include: