3 interlock sensors – Trebor IQ Chemical Heater User Manual

Page 16

Advertising
background image

PAGE 16

MODEL IQ CHEMICAL HEATER OPERATION / MAINTENANCE MANUAL

6.3 INTERLOCK SENSORS

ALARM

CAUSES

SOLUTIONS

Liquid Leak

Liquid leak detected inside

heater housing

Sensor/wiring shorted or

improperly wired to
interlock

If liquid is present in the

housing, decommission
and replace heater per
Section 5.3.

Inspect/test sensor wiring.

Element Over-

Temperature

No liquid or insufficient

flow through the heater

Insufficient control settings

or scheme

Sensor/wiring shorted or

improperly wired to
interlock

Increase flow rate.

Modify control settings or

scheme to limit the
element to

≤250°C.

Inspect/test sensor wiring.

Liquid Over-Temperature

Insufficient flow through

the heater

Insufficient control

algorithm

Sensor/wiring shorted or

improperly wired to
interlock

Increase flow rate.

Check for blockage.

Relocate outlet

temperature sensor
closer to heater outlet.

Adjust control settings or

scheme.

Inspect/test sensor wiring.

Liquid Level

Insufficient liquid present in

heater

Liquid boiling

Sensor/wiring shorted or

improperly wired to
interlock

Increase flow rate.

Review liquid properties

vs. conditions.

Adjust sensor

Inspect/test sensor wiring.