Trebor IQ Chemical Heater User Manual

Page 8

Advertising
background image

PAGE 8

MODEL IQ CHEMICAL HEATER OPERATION / MAINTENANCE MANUAL

T

e

= 236.6°C (Maximum allowable element temperature)

Example 2: Given a maximum allowable liquid temperature of 140°C, a

heater rated at 6 kW and a 75% duty cycle, the maximum
element temperature limit is:

T

e

= 140°C + (6)*(0.75)*(16.1)

T

e

= 212.5°C (Maximum allowable element temperature)

2.3.d Internal Over-Temperature Protection

The Trebor IQ chemical heater is supplied with a temperature sensor(s)
located near the top of the quartz substrate. The control system must
limit the quartz substrate temperature interlock sensor to a maximum
temperature of 200°C. Note, two types of sensors are available

thermocouple and RTD. See Section 7 for wiring instructions.

2.3.e Liquid Level Sensor Interlock

The Trebor IQ chemical heater requires a liquid level interlock with a
sensor located at the heater outlet to prevent dry operation, see Figure
2-2
for example. See Section 7 for wiring instructions

for Trebor’s

optional liquid level sensor.

Figure 2-2

Advertising
This manual is related to the following products: