Manual_GNAMG_Profibus_EN.doc 19/19

Baumer IVO GmbH & Co. KG

04.05.11

Villingen-Schwenningen,

Germany

7.2.5. Terminal

assignment

Pin M12

Terminal

Significance

Pin 1

UB

Supply voltage 10...30 VDC

Pin 3

GND

Ground terminal for UB

Pin 2

A

Negative serial data line

Pin 4

B

Positive serial data line


M12 connector
for serial data line


for power supply

1

3

4

5

2

4

3 5

1

2

male

female

1

3

4

2


Terminals the same designation are connected to each other internally and identical in their functions. The
maximum load of the internal clamps UB-UB and GND-GND is 1 A each.
(A and B are each isolated with 100 nH inductivity for 12 MBaud operation).

• Carefully press the cover of the inclination sensor over the sealing rubber, taking care not to tilt it. The

cover must fully rest against the base plate.

• Tighten both the fastening screws firmly in the same direction.

The inclination sensor housing and braided shield of the connecting cable are only ideally connected if the
cover is resting fully against the base plate (positive locking).


7.2.6. Status indicating elements (LEDs)
Bus cover provides at rear an integrated DUO LED.

Colour

Status

LED green continuous

Inclination sensor is in mode „Data_Exchange“

LED yellow continuous

Inclination sensor in ramp-up status or less bus contact



7.2.7. Profibus

cable

EN 50170 specifies two types of cables, A and B. Cable type B is obsolete and should no longer be used
for new applications. With cable type A , all transmission rates up to 12 MBaud can be used.

Features

Data

Shaft resistance in Ohm

135 to 165 at 3 to 20 MHz

Operating capacity (pF/m)

Less than 30

Loop resistance (Ohm/km)

Less than 110

Core diameter (mm)

Greater than 0,64

Core cross section (mm)

Greater than 0,34



Transmission speed depending on cable length

Baud rate in

kBaud

9,6 19,2 93,75 187,5 500 1500 3000 12000

Cable

length in m

120

0

1200 1200 1000 400 200 100 100