Operators instructions cleverlevel switch, lffs, Measuring principle mounting, Dimensions – Baumer CleverLevel - LFFS User Manual

Page 2

Advertising
background image

www.baumer.com

Operators instructions: 11109132 02 EN Page 2 / 12

Measuring principle

Mounting

Operators instructions
CleverLevel switch, LFFS

The capacity (C) of the media is directly proportional to the dielectric
value of the media.

A frequency between 100 and 180MHz is swept into the media.

When the coil (L) and the capacitor (C) reach a resonance frequency,
it will be detected by the electrical circuit.

Please refer to “Accessories” data sheet. The welding part has
an engraved mark or a leak hole. When the product has been
mounted and correctly tightened the gland or M12 plug will
align with this mark.

Make sure that the gland/plug is pointing downwards to pre-
vent fluids from penetrating into the instrument.

Use only the authorised special designed accessories. The
product warranty is void when installed with other adapters.

Do not use PTFE, fibre or other gaskets. The PEEK tip against
the stainless steel welding part will perform a hygienic tighten-
ing provided that the guidelines have been followed.

Due to the measuring principle it is essential that the sensor tip
can “see” an ample amount of the metal shaft or welding part.

Dimensions

Mounting instructions for sliding connection:

1) Clean the sliding shaft.

2) Mount the smallest ring against the media as indicated.

3) Tighten the G1/2 Hygienic sliding nipple at 25...30 Nm.

4) Replace the Washer ring kit when one or both parts are
permanently deformed or stick to the shaft of the sliding
connection.

The Level Switch LFFS with sliding connection can be mounted
in installations with a static pressure up to 16 bar.

To prevent personal injuries or property damage it is essential
that the safety wire is mounted correctly and is undamaged.

WARNING

100

or

250

Sliding

connection

2 × PEEK

sealing

washers

Spare part set:

4401.8001

Safety

wire

G½ hygienic

3A DN38 hygienic

G½ hygienic sliding connection

19,0

31,5

14,5

Advertising