Operators instructions cleverlevel switch, lffs, Electrical connection, Normally open - no normally closed - nc – Baumer CleverLevel - LFFS User Manual

Page 7

Advertising
background image

Electrical connection

Operators instructions
CleverLevel switch, LFFS

M12 plug: 1 Brown

2 White*

3 Blue

4 Black

* To avoid unintended Teach-In, be aware not to
connect the Teach-In pin or expose it to any
electrical noise during normal operation.

Normally open - NO

Normally closed - NC

Electrical specifications:
Power supply

12,5...36 VDC, 35 mA max.

Output

PNP, NPN or Digital

Max. 50 mA, short-circuit and high

temperature protected

Active “Low”

NPN and Digital output

(-VDC +2,5V) ±0,5V, R

load

1 kΩ

Active “High”

PNP and Digital output

(+VDC -2,5V) ±0,5V, R

load

1 kΩ

1

2

5

1

2

5

1

2

5

1

2

5

1

2

5

1

2

5

www.baumer.com

Operators instructions: 11109132 02 EN Page 7 / 12